DM-602-NH₃ Ammonia Sensor
Manufacturer: Teledyne| DetconDM-602-NH₃ Ammonia Sensor
Manufacturer: Teledyne| DetconDetcon Model DM-602IS-NH₃ sensor is designed to detect and continuously monitor NH₃ in air over the range 0-100 ppm.
The sensor assembly consists of an electrochemical fuel cell mounted in an Intrinsically Safe stainless steel and ABS plastic housing that includes a splashguard with integral cal port, a signal conditioning control transmitter circuit, a base connector board and an explosion proof junction box.
The Intrinsically Safe sensor housing design allows direct contact of the target gas to the electrochemical sensor, thus maximizing response time, detectability and repeatability.
And because the Intrinsically Safe housing design does not use a stainless steel flame arrestor, it eliminates inaccurate readings due to target gas absorption.
Specifications
Manufacturer
Approvals & Certifications
- CSA, UL Approved: Class I, Div. 1, Groups B, C, D
- ISO 9001: 2008
- NRTL
Communication
- RS-485 Modbus Communication Protocol
Consumption
- 2.9 W at 24 Vdc
Display
- Backlit LCD Display
Electrical Connectors
- Junction Box
Enclosure, Body Material
- ABS Plastic Housing
- Intrinsically Safe Stainless Steel Assembly
Environmental Protection
- Electrical Classification: Explosion-proof
- IP66
- NEMA 4X
Humidity
- 15 to 90% Relative Humidity, Non-Condensing
Indication
- LED Indicators for Fault & Cal Status
Input
- 22.5 - 28 Vdc
Materials of Construction
- Aluminum Junction Box
- Stainless Steel Junction Box
Measuring Range
- 0 to 100 ppm Ammonia
NPT Connection
- ¾” NPT
Operating Temperature
- -40° to 50° C (-40° to 122° F)
Output
- 4-20 mA DC (Linear)
Relay Output
- 3 Relays (Alarm 1, 2, Fault, Contacts 5 A)
Repeatability
- ± 2% of Full Scale
Response Time
- T90 < 90 seconds
Sensor, Probe Type
- Electrochemical Fuel Cell
Span Effect
- < 2% Signal Loss Per Month